Power
UPS Capacity: 1000 VA / 900 W
Input
Input Voltage Range: 110~300Vac (176~264Vac @ 100% load)
Input Frequency: 40~70Hz (50/60Hz Auto-Sensing)
Nominal Voltage: 208/220/230/240Vac
Phase: Single Phase
Power factor: ≥0.99
Output
Output Frequency:
- Online mode: 46~54Hz or 56~64Hz
- Bat. Mode: (50/60±0.1%)Hz
Transfer Time:
- AC mode to Bat.mode: 0ms
- Inverter to Bypass: 4ms (Typical)
Output Voltage: 208/220/230/240Vac
Power factor: 0.9
Output Sockets: IEC panel
Crest factor: 3:1
Harmonic distortion (THDv):
≤3% Linear load
≤5% Non linear load
Output Waveform: Pure Sinewave
Battery
Battery Type: Valve Regulated Lead Acid (VRLA)
Typical Recharging Time: 4 hours (To 90% of full capacity)
Capacity (Standard Unit): 12V/9Ah
Battery Number: 2
DC System Voltage (VDC): 24V
Charging Current (Max.): 1A
Expandable Runtime: Yes, External battery pack: DS-UPSB0924B-R/TC
Typical Backup Time: View Runtime Graph
Indicator
Alarm: Battery mode/Battery low voltage /Overload/Fault
LCD display: Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time
Efficiency
AC Mode: 90%
Battery Mode: 85%
Environment
Operating Temperature: 0°C~40°C
Storage Temperature: -25°C~55°C
Humidity Range: 20~95%RH @ 0~40°C (Non condensing)
Altitude: <1500m, derating required when>1500m
Noise Level: <55dB at 1 Meter
Physical
Dimension W x D x H (mm): 144 x 293 x 209
Net weight (kg): 9.3
Standards
Safety: CE-LVD, IEC/EN 62040-1, IEC/EN 62477-1
EMC: CE-EMC, IEC/EN 62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8