  UPS ATLANTIS A03-OP1502P 1500VA/1350W DOPPIA CONVERS., SMART BATTERY MANAG.-INTERFACCIA USB/RS232/EPO-TRIPLA BATT.12V FINO:30/04 - cod. 42.961 - A03-OP1502P - AC computer - §§§UPS ATLANTIS A03-OP1502P 1500VA/1350W DOPPIA CONVERS., SMART BATTERY MANAG.-INTERFACCIA USB/RS232/EPO-TRIPLA BATT.12V FINO:30/04 - cod. 42.961 - cod. produttore: A03-OP1502P

Power Rating (VA): 1500
Power Rating (W): 1350

Input:
- 80VAC-300VAC (load <=30%±5%)
- 120VAC-300VAC (load <=60%±5%)
- 140VAC-300VAC (load <=80%±5%)
- 160VAC-300VAC (load <=100%±5%)
Frequency Range: 40Hz to 70Hz
Power Factor: >0,99 (Normal Voltage)

Output:
- Voltage: 208/220/230/240VAC
- AC Voltage Regulation: ±1% 
- Frequency Range: 50Hz (±0.5%) or 60Hz (±0.5%)
- Waveform: Pure SineWave
- Crest Ratio Current 3:1 (Max)
- Harmonic Distortion (THDU): min 3% THD (liner Load) / min 5% THD (Non liner Load)

Transfer:
- AC->Battery: Zero
- INV->ByPass: Less than 4ms (typical)
WaveForm (Batt. Mode): Pure Sinewave

Efficiency:
- AC Mode = 89%
- Battery = 85%
- ECO = 97%

Battery:
- Voltage: 36VDC
- Capacity: 12V/9.0Ah
- Quantity: 3
- Recharge Time: 4 hours to (90%)
- Type: Sealed Maintenance Free Lead Acid VRLA Type
- Design: Swappable battery design
- Charging Voltage: 41,1VDC ±1%
- Charging Current: 1.5A Max

Indicators (display LCD):
- UPS status, Load level, Battery level, Input/Output/battery info, Discharge time and Fault indicators

Backup Time:
- 1350w up to 2:30m
- 1013w up to 5:30m
- 675w up to 9:30m
- 338w up to 22m

Protection:
- 105% < Overload AC <110% Overload Warning UPS Only
- 110% < Overload AC <130% Overload Warning UPS transfers to ByPass after 1 minutes
- Overload AC >130% Overload Warning UPS transfers to ByPass after 3 seconds
- 105% < Overload Battery <110% Overload Warning UPS
- 110% < Overload Battery <130% Overload Warning UPS shut down after 1 minute
- Overload AC >130% Overload Warning shut down after 3 seconds
- 110% < ByPass <120% Overload Warning UPS shut down after 30 minutes
- 120% < ByPass <130% Overload Warning UPS shut down after 10 minutes
- ByPass >130% Overload Warning UPS shut down after 1 minute
- Overload Inverter (>100%)
- Short Circuit INV: Electric Circuit
- Short Circuit AC: ICB & Electric Circuit
- Battery Over-drain Two stages: Controlled Battery Low Warning & Cut Off
- High Surge Level Immunity (>7KV)
Advanced: Fan detect protection and Fan speed control | ECO mode

Connections:
- Output 4xIEC 320 C13 (Battery Power Supplied)
- RS232 and USB(HID)
- Intelligent Slot for SNMP Card
- EPO/ROO
- Battery Bank Connection

Dimensions (WxHxD): 151 x 225 x 394 mm
Net Weight 16,5 Kg (with Battery)
Temperature: 0°-40° C
Humidity: Humidity 20-90% (non-condensing)



Salvo errori e/o omissioni. ©AC computer - Tutti i diritti riservati.